UL 489A - DC circuit breakers for telecommunications (USA)

DC circuit breakers up to 600 V for branch-circuit protection in telecommunications equipment (USA).

Rodzaj
Approvals, marks and certification standards
Organizacja
UL Standards & Engagement
Aktualne wydanie
UL 489A Edition 1 (2008-10-15), text including revisions dated June 26, 2023
Status
current

What the standard covers

The standard covers single- and multipole circuit breakers rated up to 600 V DC, intended for overcurrent and short-circuit protection of branch circuits in DC-powered communications equipment, for example base stations.

All poles of a multipole circuit breaker operate at the same potential. The standard supplements UL 489 and modifies the tests described in the base standard.

What the certificate demonstrates

UL 489A certification confirms that a DC circuit breaker provides branch-circuit overcurrent and short-circuit protection in telecommunications equipment for the US market. The standard permits DC voltage ratings only and does not permit slash voltage ratings (Clause 15.1); an interrupting rating other than 5000 A must be marked on the circuit breaker (Clause 16.6).

The certification applies to use in communications equipment; full approval for branch-circuit protection in a general NEC installation requires UL 489 certification. In the EU, the certificate does not replace assessment to IEC/EN 60947-2.

How certification is performed

Construction is evaluated to UL 489, with the exceptions in Sections 5–7: insulation spacings within the circuit breaker are evaluated to UL 489 (after installation, compliance with end-product spacings is sufficient); terminals may be connectors, screws, studs or spring terminals matched to the end-product part; manual opening and closing is required, and the use of an ordinary tool is permitted.

Tests (Sections 8–14) are performed to UL 489 with modifications: calibration to UL 489, and where the ambient temperature differs from 25 °C or 40 °C, additional calibration at the temperature marked on the product (for a temperature range, at the extreme values); overload at 150% of rated current in a circuit with a time constant of at least 0.003 s; temperature test without tripping until temperatures stabilize; endurance of 1000 make-break cycles under load or the lower number of operations specified in the UL 489 table; interruption testing to UL 489, where prospective current may be any value required by the application and the test current in sequence Y does not exceed the circuit breaker's rated short-circuit capacity; elevated-temperature conditioning at 100 ±2 °C for 7 h, followed by repeat calibration without exceeding allowable trip times.

Products are certified under the UL Listing system with production surveillance.

Scope, classes and levels

  • rated voltage up to 600 V DC; DC ratings only, no slash ratings
  • poles of a multipole circuit breaker at the same potential
  • overload: 150% of rated current, circuit time constant ≥ 0.003 s
  • endurance: 1000 make-break cycles under load or the lower number specified in the UL 489 table
  • elevated-temperature conditioning: 100 ±2 °C for 7 h, followed by calibration testing
  • interrupting-test current in sequence Y: not greater than the circuit breaker's rated short-circuit capacity
  • markings: ambient temperature other than 25/40 °C, “SAME POLARITY” where reduced spacing to an auxiliary circuit is used, and interrupting rating other than 5000 A

What to check in the datasheet and certificate

Check whether the datasheet distinguishes UL 489 from UL 489A; for UL 489A, identify the UL file number, certified DC voltage, marked interrupting rating (marking is required for a value other than 5000 A), and the ambient-temperature range marked on the breaker, because calibration at a temperature other than 25 °C or 40 °C is performed at the marked temperature.