The insulation monitoring relay continuously monitors the insulation resistance of an unearthed IT system relative to the protective earth conductor. In an IT system, the first earth fault does not interrupt the power supply and may remain unnoticed until a second earth fault occurs. The relay detects the first fault at an early stage and signals it at two independently adjustable thresholds: prewarning and alarm. This allows the fault to be rectified during scheduled maintenance. In DC systems, the display indicates the affected pole, “+” or “-”, helping to locate the fault more quickly.
The measuring system operates in AC, DC and mixed AC/DC networks at frequencies up to 1000 Hz and with system leakage capacitance of up to 1000 µF. Such capacitance to earth can result from EMC interference suppression filters in circuits containing power converters. The relay also monitors insulation in de-energised networks. Settings are adjusted using two rotary controls on the front panel, while the display shows the insulation resistance and system voltage. A transparent sealable cover protects the settings against unauthorised changes.
Traction converters and auxiliary converters in railway vehicles
Traction converters, auxiliary converters and battery chargers supply unearthed electrical systems within railway vehicles, including the 110 V DC battery bus and AC auxiliary circuits. DOLD recommends connecting the measuring circuit at the primary power supply point: on the DC side in battery systems with an inverter, or on the AC side in systems with a transformer or generator and rectifier. The relay monitors three-phase, four-wire networks via the neutral point (3NAC mode). An earth fault on the opposite side of a converter can be detected if a current greater than 10 mA can flow through the semiconductor junctions.
Vehicle battery network
The relay monitors 110 V DC networks without requiring a coupling device. The auxiliary supply voltage can be taken directly from the monitored network, provided that it falls within the auxiliary voltage range of the selected device version.
Traction substations and trackside cabinets
In auxiliary power circuits configured as IT systems, the Y1/Y2 output, galvanically isolated from the other circuits, activates the DOLD RR 5886 / RR 5887 insulation fault location system. The output is activated when the insulation resistance falls below the alarm threshold.
Monitoring via the control system: RN 5897/011
The RN 5897/010 provides status information through two changeover contacts: prewarning and alarm. When the vehicle control system or substation SCADA system needs to record the actual insulation resistance value, the RN 5897/011 is the appropriate version. It features the same measuring system supporting leakage capacitance of up to 1000 µF and a galvanically isolated Modbus RTU interface for reading measured values, adjusting settings, performing tests and resetting the device.
Technical specifications (RN 5897.12/010/61, according to the datasheet)