Limitor® aSJB/D 3.6–12 kV with Striker

Medium-voltage back-up fuse-links rated 3.6–12 kV and 32–430 A, with a 20 N / 20 mm striker. Compliant with IEC 60282-1 and IEC 60644, dimensions according to DIN 43625. When a fuse-link operates, the striker mechanically actuates a microswitch or trip coil so that operation of a single fuse opens the entire switching device and is visible to the diagnostic system.

In 3.6 kV versions, the family includes, among others, 45ASB36V125P-1 (Y076473, 125 A, 192 mm long) and 45ASB36V160P-1 (Z076474, 160 A, 192 mm) - used in onboard medium-voltage circuits of vehicles supplied from 3 kV DC networks. Operation indication is provided by an MC1-5N series microswitch with a FLEX lead.

The datasheet specifies minimum breaking current, power losses, I²t values and weight for each fuse-link - selection for a specific converter is based on these parameters.

Key features:

  • Back-up class, 3.6–12 kV, rated currents 32–430 A
  • 20 N / 20 mm striker - operation of one fuse-link opens the entire switching device
  • Compliance with IEC 60282-1 and IEC 60644, dimensions according to DIN 43625
  • 3.6 kV versions: 45ASB36V125P-1 (125 A) and 45ASB36V160P-1 (160 A), length 192 mm
  • Operation indication via MC1-5N series microswitch with FLEX lead

Product standards